Cycle Sensor Pump Monitor: Specifications
Features
- Digital readout of current and set points
- More accurate than standard pump protection
- Set points are stored on power loss
- Adjustable rapid cycle set point
- Manual reset on rapid cycle
- Adjustable dry run set point
- Adjustable restart delay on Dry Run
- Optional lock protection feature
- Compact size
Model CS1PH1-2HP
Input voltage | 190-264 vac (230V) |
Frequency | 50- to 60 hz |
Output rating | 1/3 to 2HP at 240 vac |
Horse power ranges | 1/3 to 2HP |
Dry run adj range | 1.0 to 15.0 amps |
Dry run trip delay | 10 seconds |
Restart delay range | 1-300 min; 0 for manual reset |
Rapid cycle adj range | 0 to 600 seconds |
Ambient operating temp | -4 to 122 degrees F |
Dimensions | 4.524 X 3.524 X 1.750 (LWH) |
Model CS1PH3-15HP
Input voltage | 190-264 vac |
Frequency | 50- to 60 hz |
Output rating | 600 VA at 240 vac |
Horse power ranges | 3 to 15HP |
Dry run adj range | 10 to 75 amps |
Dry run trip delay | 10 seconds |
Restart delay range | 1-300 min; 0 for manual reset |
Rapid cycle adj range | 0 to 600 seconds |
Required CT ratio | 50 : 5 |
Ambient operating temp | -4 to 122 degrees F |
Dimensions | 4.524 X 3.524 X 1.750 (LWH) |
Model CS3PH1-500HP
Control voltage | 95-132 vac (115 volt range) 190-264 vac (230 volt range) |
Frequency | 50- to 60 hz |
Output rating | 600 VA at 240 vac |
Horse power ranges | 1 to 500 HP (CT's required) |
Dry run adj range | 0 to 7.5 amps (50:5 CT w/10 passes) 7.6 to 37.5 amps (50:5 CT w/2 passes) 38-75 amps (50:5 CT w/1 pass) 75 to 375 amps (250:5 CT w/1 pass) 376 to 750 amps (500:50 CT w/1 pass) |
Dry run trip delay | 10 seconds |
Restart delay range | 1 to 300 min; 0 for manual reset |
Rapid cycle adj range | 0-600 seconds |
Ambient operating temp | -4 to 122 degrees F |
Dimensions | 4.524 X 3.524 X 1.750 (LWH) |